Inspection, testing, servicing, and other maintenance of sprinkler systems must be - ANSWERSpersonally supervised and be performed in accordance with NFPA (National Fire Protection Association) #25 2011 edition.
Automatic and non-automatic sprinkler systems shall be inspected, tested and maintai...
Inspection, testing, servicing, and other maintenance of sprinkler systems must be - ANSWERSpersonally
supervised and be performed in accordance with NFPA (National Fire Protection Association) #25 2011
edition.
Automatic and non-automatic sprinkler systems shall be inspected, tested and maintained as required by
NFPA #25 2011 edition by - ANSWERScompetent person holding a S-12 Certificate of Fitness and
employed or contracted by the owner
How long must maintenance records be kept? - ANSWERSMinimum 3 years
If there are 300 sprinkler heads or less how many spares must be kept on premises - ANSWERSAt least 6
How often do sprinkler connections need a hydrostatic pressure test? - ANSWERS5 years
Who maintains the records of inspections, tests, servicing, and other items of maintenance? -
ANSWERSImpairment coordinator
Who assigns the impairment coordinator - ANSWERSBuilding owner
Under what conditions should the fire department be notified regarding a system that is out of service? -
ANSWERS- out of service on more than 1 floor of a building or
- the repair cannot be completed in less than 8 hours or
-there are one or more fire protection services out of order at the same time
When the Cof holder observes a minor defect, he shall report the condition to the ____ ____ and if it is
not corrected within ____ days it shall be deemed an ____ and reported in _____ to the ____ ____. -
ANSWERSBuilding owner, 30, impairment, writing, FD
,Systems that are out of service, both planned and unplanned shall be identified by placing a tag on the
following locations: - ANSWERS- FD connections
- system control valves
- fire command center
- or clear visible location in lobby ofbuilding
Who is required to post tags at the main control valve? - ANSWERS- master fire suppression contractor
(class a or b)
-master plumber
Where would a green tag be placed? - ANSWERSMain control valve
If a system is fully out of service, what color and where should tags be placed? - ANSWERS- white disc on
all affected fire department connections
- red disc on main control valve
If a system is particularly out of service, what color and where should tags be placed? - ANSWERS-Blue
disc on all affected fire department connections
- red disc on main control valve
What should the red tag on the main control valve include? - ANSWERS- sprinkler company name
- date of removal from service
- anticipated working date
What should the tags indicate? - ANSWERS- area affected
- brief description of condition
-occupancy classification
- COF #
- est. time system will be operational
, What color are tags if no impairment is found? - ANSWERSGreen
Who are the ONLY people permitted to place a tag on a underground service main, water storage tank,
control valve, fire department connection, or booster pumps? - ANSWERSFDNY, owner, MFSPC or Master
plumber
Approved nonfreezing solutions include glycerin not greater than---- and glycon greater than ---- non
freezing solution - ANSWERS48%/38%
What is a riser card - ANSWERSAn approved card baring the dates of inspection, COF #, and signature of
COF holder.
Where should the riser card be placed? - ANSWERSOh the premesis near the main water supply control
valve
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH _________
SPRINKLER HEADS OR LESS. - ANSWERS30
Alarm Notification Appliance - ANSWERSA fire alarm system component, such as a bell, horn, speaker,
light, text display or vibration device that issues an audible, tactile, and/or visual alert
Alarm signal - ANSWERSA signal indicating an emergency requiring immediate action, such as a signal
indicative of fire.
Antifreeze Sprinkler System - ANSWERSA wet pipe sprinkler system employing automatic sprinklers that
are attached to a piping system that contains an antifreeze solution and is connected to a water supply.
The antifreeze solution is discharged, followed by water, immediately upon operation of sprinklers
opened by heat from a fire.
AUTOMATIC BALL DRIP DEVICES SHALL BE INSTALLED IN THE _________ POSITION. - ANSWERShorizontal
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller papersmaster01. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $14.99. You're not tied to anything after your purchase.