Nicet Level 1 AND 2 TESTS
When a device is inaccessible due to excessive height, such as an atrium, what it the
maximum interval for testing? - CORRECT ANSWER 18 months
When installing a wall-mounted fire telephone appliance to the public, what is the
acceptable maximum mounting height from t...
When a device is inaccessible due to excessive height, such as an atrium, what it the
maximum interval for testing? - CORRECT ANSWER 18 months
When installing a wall-mounted fire telephone appliance to the public, what is the
acceptable maximum mounting height from the floor? - CORRECT ANSWER 66 inches
Elevator lobby smoke detectors shall be mounted within a maximum of which distance
from the center-line of the door? - CORRECT ANSWER 21 feet
At minimum, when working near power lines with voltage of 600 volts and lower, an
aerial lift operator shall maintain which distance from the lines? - CORRECT ANSWER
10 feet
The use of unprotected EMT shall be permitted under which conditions? - CORRECT
ANSWER when in direct contact with the earth
According to NFPA 70, what is the maximum unsupported length of 1/2-inch flexible
metallic conduit where flexibility is required after installation? - CORRECT ANSWER 4
1/2 feet
What is the maximum bend (in degrees) permitted in a conduit run between outlet
boxes? - CORRECT ANSWER 360 Degrees
If the primary power is disconnected and the fire alarm system goes into an alarm
condition, what is the minimum acceptable time for secondary power to operate the
voice evacuation systems? - CORRECT ANSWER 15 minutes
A riser room temperature switch should activate when the temperature falls below which
level? - CORRECT ANSWER 40 degrees F
According to NFPA 72, what is the maximum sound pressure level permitted in a space
with notification appliances? - CORRECT ANSWER 110 dBA
What is the minimum interval for testing a single-station smoke detector in multifamily
units? - CORRECT ANSWER Annually
Where should a technician install a detector in relation to beam that is less than 12
inches deep and less that 8 feet in center? - CORRECT ANSWER At the bottom of the
beam
,An existing fire alarm cable in a drop ceiling will be spliced. which one of the following
splice locations will comply with NFPA 70? - CORRECT ANSWER secured inside a
listed box or enclosure
Which function shall be tested for each newly installed smoke detector? - CORRECT
ANSWER smoke entry?
An 180 foot long corridor is 10 feet wide, with a smooth 10 foot ceiling, interrupted by 4-
inch beams spaced every 10 feet. How many heat detectors with a listed 30 foot
spacing are required? - CORRECT ANSWER 6 heat detectors
At which height must cables be physically protected when being installed within an
exposed ceiling? - CORRECT ANSWER 7 feet
When shall smoke detectors be installed during the construction process? - CORRECT
ANSWER After the final cleanup of all trades
Where structural members are provided, intermediate metal conduit shall be secured
within which maximum distance from an outlet box" - CORRECT ANSWER 3 feet
The requirement forbidding fire alarm circuits from being T-tapped, unless indicated by
the manufacturer's instructions, is intended to prevent which type of improper
malfunction? - CORRECT ANSWER monitoring integrity of installation conductors?
What is the maximum operating temperature of TW insulation? - CORRECT ANSWER
140 Degrees F, Table 310.15 (B)(16)
Which type of meter is used to measure the current draw of a strobe circuit? - CORRECT
ANSWER multimeter
What is an acceptable document for finding information on spacing of video imaging
smoke detection systems? - CORRECT ANSWER shop drawings in submittal package
When pulling multiple cable through a junction box, the installer must leave which
minimum length of wire for splicing? - CORRECT ANSWER 6 inches of wire
Which three of the following conditions are symptoms of a heart attack? - CORRECT
ANSWER heartburn, pain in chest, shortness of breath
Sprinkler water storage containers shall be supervised to indicate what the water
temperature drops to which level? - CORRECT ANSWER 40 degrees F
According to NFPA 72, what is the minimum separation between outgoing and returning
conductors for a Class A loop that is horizontally placed down to an 8 foot-wide
corridor? - CORRECT ANSWER 4 feet of separation
, According to NFPA 72, a public emergency alarm reporting system shall operate its
emergency power source for which minimum time period? - CORRECT ANSWER 10
minutes
Where shall employers post a safety data sheet? - CORRECT ANSWER in the
technician's work area
According to NFPA 72, during an acceptance test, which method can be utilized for
testing a sprinkler waterflow switch? - CORRECT ANSWER Open the inspector's test
valve to cause an actual flow of water, ensure that the control panel receives the alarm
within 90 seconds
I'm technicians are working in a plant, remind to learn of the plants safety regulations? -
CORRECT ANSWER from OSHA regulations?
When into a telephone communication system is required, at least one telephone or
Jack shall be installed in which of the following locations? - CORRECT ANSWER in a
fire pump room
Who is responsible for fire alarm system and testing and maintenance? - CORRECT
ANSWER Property owner
In a protected premises with a 40 foot long by 15 foot wide room having a smooth
ceiling, what is the minimum quantity of smoke detectors that shall be required? -
CORRECT ANSWER 2 smoke detectors
A meter will be used to measure a horn strobe circuit current draw. Which of the
following statements is correct? - CORRECT ANSWER The meter should be connected
in series with the circuit; it must be located before the first device(horn or strobe). ?
Which plans include a fire detection system details? - CORRECT ANSWER electrical
Wall-mounted audible signal appliances shall be mounted how many inches below
finished ceiling? - CORRECT ANSWER 6 inches minimum
A Crew member has a suspected leg fracture. Before moving the crew member, what is
the recommended first step I'm treating the injury? - CORRECT ANSWER Immobilize
the leg
How often shall alarm notification appliances be tested? - CORRECT ANSWER Every
12 months
We're the outgoing and return conductors enter or exit notification of clients, the
conductors are permitted to run in the same cable assembly for up to which maximum
distance? - CORRECT ANSWER 10 feet?
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller GEO888. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $22.49. You're not tied to anything after your purchase.