NICET LEVEL 1 EXAM/86 ANSWERED
QUESTIONS
4 wires - -what is the maximum number of 14 AWG RHH conductors which
can be installed in 1/2 rigid metal conduit?
-3.5'-48" to the actuator - -Which of the following would be an appropriate
mounting height for a pull station?
-1 flash per second - -What is the minimum flash rate for a visible
notification device?
-90" to the top of the device - -What is the minimum mounting height for
audible notification devices?
-Such that the entire lens is not less then 80" - -What is the minimum
mounting height for visible notification devices?
-Voltage=Current X Resistence - -What is the formula for Ohm's Law
-Put your meter in series with the circuit - -When using your mult-meter to
measure, you must:
-Semi-annually - -Waterflow devices shall be tested with that frequency?
-Annually - -With what frequency shall ionization smoke detectors be given
a functional test?
-24 hours in normal operation, 5 minutes in alarm - -What are the standby
power requirements for a proprietary signaling system?
-Shunt type - -Which of the following is a type of auxiliary protective
signaling system?
-A UL listed central station
A receiver located at an unlisted monitoring facility
A fire department or communications center - -Remote station signaling
systems are permitted to send signals to:
-600V - -Non-power limited fire alarm cable shall have an insulation rating
of:
-20,000 CFM HVAC system serving a single floor
15,000 CFM HVAC system serving 3 floors
, 20,000 CFM HVAC system serving 2 floors - -Which of these HVAC systems
would require duct detectors on supply and return?
-Group A, E, F - -According to the IBC, which of the following use Groups
require visual notification?
-Every 4 hours - -Digital Alarm communicator transmitters (DACT) which
use call forwarding to the DACR shall be tested with what frequency?
-True - -When connecting 4 wires smoke detectors to a fire alarm system,
the power conductors shall be monitored for integrity.
-Smoke detectors shall be permitted to use 30 foot spacing as a guide - -
Which of the following is true regarding smoke detector spacing?
-A slope of greater than 1 in 8 - -A slope ceiling is defined as:
-Fire alarm control equipment shall be protected with an automatic detector
when not in continuously occupied areas
Positive alarm sequence requires the approval of the AHJ
FPLP cable may be substituted with CMP cable - -Which of the following is
true?
-Alarm signal
Trouble signal - -For sprinkler systems what type of signal is fire pump
running?
-A dedicated branch circuit - -consider a fire alarm system with primary
power source as commercial light power. what type of branch circuit is
permitted to supply the fire alarm system?
-Multimeter - -what is type of meter is typically used to measure current in
a fire alarm system
-750 feets - -where an auxiliary fire alarm system uses a shunt loop, it shall
not exceed a length of _______feets.
-Building Owner - -software information and as built drawing shall be
maintained for the life of the system by which of the following?
-2.54 ohms - -what is the wire resistance in ohms of 500 feets of 16 awg
solid copper which is coated at 75 degrees C?
-indirect pressure - -which of the following concerns the use of pressure
points in the body to help control bleeding?
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller Nursephil2023. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $10.49. You're not tied to anything after your purchase.