Type ____ is multiconductor cable identified for use as underground service entrance cable. - ANSWERType USE cable
Knife switch rated for more than 1200 Amps at 250Volts or less - ANSWERCan be used only as isolating switch, shall not be opened under load
Track lighting with outlets in a bathr...
Type ____ is multiconductor cable identified for use as underground service entrance cable. -
ANSWERType USE cable
Knife switch rated for more than 1200 Amps at 250Volts or less - ANSWERCan be used only as
isolating switch, shall not be opened under load
Track lighting with outlets in a bathroom is not allowed because ? - ANSWERTrack lighting has
receptacle
Where internal combustion engines are used as the prime motor, an on site fuel supply shall be
provided with an on premise fuel supply sufficient for not less than ____ hours full demand
operation of the system - ANSWER6 hours
Fixed in place X-ray equipment properly supplied by a branch circuit rated at not over ____ amperes
shall be permitted to be supplied through a suitable attachment plug cap and hard service cable
cord. - ANSWER30 Amps
Where skin effect exist the ferromagnetic envelope shall be bonded at ____. - ANSWERBoth ends
GFCI protection at a carnival is not required for equipment at circuit if the receptacle is of the
____type. - ANSWERLocking
The maximum voltage drop from service point to the last over-current device in a dwelling unit? -
ANSWER4%
Which of the following statements best describe the grounding requirement for central vacuum
outlet - ANSWERAccessible non current carrying metal parts are required to be connected to an
equipment grounding conductor.
In healthcare facilities, patient bed receptacles located in general care areas shall be supplied by at
least two branch circuits, which ____permitted to originate from two separate transfer switches on
the emergency system - ANSWERAre permitted
,Patient care areas of healthcare facilities ____ areas such as business offices, corridors, lounges ,day
rooms, or similar areas - ANSWERDo not include
The patient care area is any portion of the healthcare facility where patients are intended to be
____or ____. - ANSWERExamined or treated
Each general care area patient bed location in a healthcare facility must be provided with four ____
or ____ duplex receptacles - ANSWERSingle or two
A hospital is a building or portion thereof used for medical, psychiatric,obstetrical , or surgical, care
on a 24 hour basis of ____ or more patients - ANSWERFour
Where installed to reduce electrical noise for electronic equipment, electrical continuity of the metal
raceways shall not be required and metal raceway can terminate a (an) ____ nonmetallic fitting or
spacer on electronic equipment - ANSWERListed fitting
Feeder and branch circuit conductors within ____ inches of a Ballast shall have an insulation
temperature rating not lower than 90°C (194°F) unless supplying a luminaiere marked as suitable for
a different insulation temperature - ANSWER3 inches
Manufactured wiring systems constructed with type MC cable shall be supported and secured at
intervals not exceeding ____ ft. - ANSWER6 ft
Where a main bonding jumper or a system bonding jumper is a screw only the screw shall be
identified with a ____ that shall be visible with the screw installed - ANSWERGreen finish
Plug fuses a 15 amperes and lower rating shall be identified by a ____ configuration of the window,
cap, or other prominent part to distinguish them from fuses of higher ampere rating -
ANSWERHexagon
The load for household electric clothes dryer's in a dwelling unit(s) shall be either ____ watts (volt-
amperes) or the nameplate rating, which ever is larger, for each dryer served ? - ANSWER5000 watts
Service conductors installed as unjacketed multiconductor cable shall have a minimum clearance of
____ windows that are designed to be opened, doors, porches, stairs fire escape or similar locations.
- ANSWER3 ft (36 inches)
, —— Cartridge fuses of the renewable type shall be permitted to be used only for replacement in
existing installation is where there is no evidence of over-fusing or tampering. - ANSWERClass H
Branch circuit conductors within ____inches of the ballast shall have an insulation temperature rating
not lower it 90°C 194°F - ANSWER3" inches
The minimum radius of a field bend on trade size 1 "1/4 RMC is ____. - ANSWER8
In a dwelling unit which appliance is allowed to have a 24"inch cord with Attachment ground plug ? -
ANSWERCombination range hood/microwave oven
Type 3 Surge Protective devices can be installed on the load side of a branch circuit overcurrent
device up to the equipment served.if ____ the type 3 SPD connection must be a minimum 30'ft of
conductor a distance from the service or separately derived system disconnect - ANSWERIncluded in
the manufactures instructions
Which flexible cable is Allowed to be used for electric vehicle charging station 300 Volts ? -
ANSWEREVJ
Type ____ fuse adapters shall be designed so that once inserted in a fuse holder that cannot be
removed - ANSWERType S fuse
Service drops Installed over roof shall have a vertical clearance of ____ above the roof surface, and
unless a lesser distance is permitted by and exceptions - ANSWER8'ft
Class 2 and Class 3 circuits shall not be placed in any enclosure, raceway, cable, or similar fittings with
conductors of Class 1 or electric light or power conductors, unless ____. - ANSWERSeparated by
barrier
In the critical care areas of health care centers, each patient bed shall be provided with a minimum
of ____ duplex receptacles - ANSWER3 duplex (6 single)
The equipment system shall supply major electric ____ necessary for patient care and basic hospital
operation - ANSWEREquipment
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller ClassRep2. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $13.99. You're not tied to anything after your purchase.