100% satisfaction guarantee Immediately available after payment Both online and in PDF No strings attached
logo-home
Oklahoma Electrical Practice Tear Exam 2024/2025 Questions With Completed & Verified Solutions. $10.99   Add to cart

Exam (elaborations)

Oklahoma Electrical Practice Tear Exam 2024/2025 Questions With Completed & Verified Solutions.

 1 view  0 purchase
  • Course
  • EWRB
  • Institution
  • EWRB

Oklahoma Electrical Practice Tear Exam 2024/2025 Questions With Completed & Verified Solutions.

Preview 2 out of 7  pages

  • October 6, 2024
  • 7
  • 2024/2025
  • Exam (elaborations)
  • Questions & answers
  • EWRB
  • EWRB
avatar-seller
ALICE12
Oklahoma Electrical Practice Tear

Wiring located within the cavity of a fire rated assembly, but not considered part of the fire rated
assembly is allowed to be... - ANS Supported by independent support wires.

A 24-volt system needs a smallest working depth of... - ANS 3 feet

All of the subsequent are acceptable forms of hearing protection EXCEPT - ANS Cotton
inserted into the ear

If a metal underground water pipe is utilized for grounding, it will have a smallest or how many
feet in contact with the earth? - ANS 10 feet

There are 6 current carrying wires in a conduit. The bonding wire is... - ANS Not counted in the
adjustment fit factor

What's the largest over current protection for a branch circuit that supplies a single non-motor
operated utilization equipment in an occupancy? The utilization rating is 20 amps. - ANS 20
amps

An underwater junction box for a 12-volt lighting system in a swimming pool is connected with a
PVC conduit. It is a flush deck box. To meet the NEC it MUST... - ANS Be filled with a potting
compound

Alternating current means the direction... - ANS Pulses Intermittently

A pool has an underwater speaker system. The PVC conduit runs in to the forming shells must
have copper wire sized at.... - ANS #8 AWG

What's the largest ampacity/breaker size for an aluminum AWG type TW #10? - ANS 25 amp
Breaker

An electromotive force is measured in... - ANS Volts

The ampacity of a 15 foot feeder tap wire that supplies a panel board must be a minimum of... -
ANS 1/3 the ampacity of the feeder.

What will be the smallest space between multiple rods or pipes grounding electrodes? - ANS 6
feet

What's the largest size branch circuit allowed to feed the line side of a transformer for a 30 volt
lighting system? - ANS 25 amps

, A bedroom in a residential unit will have a 15 amp or 20 amp receptacle set in every wall
space.... - ANS 2 feet or more in width.

What's the smallest depth for direct burial cable operating 600v or less in all unspecified
locations? - ANS 24 inches

A single family residence has a net calculation of 22,800 VA. Voltage is 240v single phase. The
feeder load is.... - ANS 95 amps.

One advantage a 24v device has over a 12v device is... - ANS It has a lower current draw

A hospital he a grounding point in a critical care area adjacent to the patient vicinity. What is the
smallest ground wire size allowed? - ANS #10 AWG

Surface mounted fixtures which contain ballasts are to be mounted on a low density cellulose
fiber board ceiling. They MUST be a minimum of how far from the surface of the fiber board? -
ANS 1 & 1/2 inches

What's the largest allowed branch circuit OCP for a 240v, 4500w, 50 gallon water heater? - ANS
25 amps

What color is utilized to mark the wire having the higher voltage to ground for a switch board or
panel board supplied from a 3-phase, 4 wire delta system? - ANS Orange

Metal conduits entering service equipment enclosures with concentric or eccentric knock outs
containing service wires will have... - ANS Bonding bushings and jumpers

What's the voltage to ground on the "A" phase of a 240v, 3 phase, 4 wire system? - ANS 120
volts

A 2" conduit enters the east side of a pull box and exits on the west side of the same box. The
smallest space from the east wall to the west wall of the pull box is how many inches? - ANS 16
inches

Other than class II conductors, lighting systems operating at 24v will have their transformer
secondary current limited to a largest of... - ANS 25 amps

A transformer has a 75 kva rating and is 460v, 3 phase with an efficiency of 90°. What is the
ampacity necessary for the primary wire? - ANS 104.6 amps (75kva/(460*1.72*90))

A jewelry store has two 15' show windows, one on either sides of the entrance way. What's the
smallest number of receptacles necessary to service these windows? - ANS 2 per window.

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller ALICE12. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?

No, you only buy these notes for $10.99. You're not tied to anything after your purchase.

Can Stuvia be trusted?

4.6 stars on Google & Trustpilot (+1000 reviews)

80435 documents were sold in the last 30 days

Founded in 2010, the go-to place to buy study notes for 14 years now

Start selling
$10.99
  • (0)
  Add to cart