NFPA-99 Practice Exam Test Questions with Latest Update
3 views 0 purchase
Course
Gas Master
Institution
Gas Master
Under which of these conditions shall the instrument Air Reserve header cylinders be permitted to be stored with the instrument air compressor?
A) the mechanical equipment room does not contain a boiler.
B) the medical air compressors are in the same room.
C) the only motor-driven machinery in ...
NFPA-99 Practice Exam Test Questions
with Latest Update
Under which of these conditions shall the instrument Air Reserve header cylinders be
permitted to be stored with the instrument air compressor?
A) the mechanical equipment room does not contain a boiler.
B) the medical air compressors are in the same room.
C) the only motor-driven machinery in the room is for instrument air equipment.
D) the room is secured with lockable doors. - Answer-C) The only motor-driven
machinery in the room is for the instrument air equipment
Riser valves are those valves located where?
A) adjacent to the main riser downstream of any zone valve.
B) anywhere in the lateral branches of the piping system.
C) in the mainline adjacent to the base of the riser.
D) in the riser adjacent to the mainline. - Answer-D) In the riser adjacent to the main line
When is the initial pressure test conducted by the installer?
A) after blowdown of the distribution piping.
B) after installation of alarm sensors.
C) before blowdown of distribution piping.
D) before installation of station rough in assembly. - Answer-A) After blow-down of the
distribution piping.
In those portions of systems intended to handle oxygen at pressure greater than 350 psi
the inter connecting hose shall not contain what materials?
A) brass.
B) copper
C) polymeric
D) stainless steel - Answer-C) Polymeric
The tool shown here allows the installer to mechanically limit the makeup depth of the
fitting to be brazed. Under what condition is this method permitted for the installation of
medical gas piping?
A) only on final line connectors.
B) only on vacuum systems.
C) where only B cup 5 brazing rod is used
D) where the limited makeup depth is not less than minimum cut depth her ANSI /
ASME recommendations - Answer-D) Where the limited makeup depth is not less than
minimum cup depth current ANSI\ASME recommendation
What is the standard gauge pressure for nitrogen gas service?
A) 15 - 30
B) 50 - 55
, C) 162 185
D) it varies with system type. - Answer-C) 50 - 55 psi
What is a NFPA 99 requirement for labeling of pipes in medical gas system?
A) color coding
B) fixed label with
C) label shall wrap completely around pipe.
D) reflective label - Answer-A) Color coding
A wireless communication device is employed in a medical gas or vacuum warning
system. what type of supervision is required for this device?
A) a visual indicator Shelby located in maintenance officer or engineering department.
B) this device shall be installed at the medical gas or vacuum source.
C) this device shall be located at nurses station.
D) this device will be supervised such that failure communication shall initiate an alarm.
- Answer-D) This device will be supervised such that failure of communication shall
initate an alarm
In a facility where Medical Gas vacuum systems are present and the failure of such
equipment or systems is likely to cause any major injury or death to patients or
caregivers this system shall be designed to meet which category requirements?
A) 1
B) 2
C) 3
D) 4 - Answer-A) category 1
A faculty is in the planning stages of installing an emergency oxygen service connection
(ESOC). How many feet is the minimum amount of clearance required around this
connection?
A) 1 foot
B) 3 feet
C) 5 feet
D) Clearance must be 1-1/2 times the width of the auxiliary. - Answer-B) 3 feet
Wooden rack for cylinder storage may be permitted under which conditions?
A) the wooden must be painted.
B) they are permitted with no set conditions .
C) they must be located in an area with fire suppression system.
D) Wooden racks are no longer permitted - Answer-D) Wooden racks are no longer
permitted
If nonmetallic flexible connectors is being used in a category 1 healthcare faculty to
connect to the manifold to the gas distribution piping what is the maximum length
permitted for the flexible connectors?
A) 2.5 feet
B) 5 feet
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller lectknancy. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $16.49. You're not tied to anything after your purchase.