100% satisfaction guarantee Immediately available after payment Both online and in PDF No strings attached
logo-home
Second Year IEC Final Exam Questions and Answers 2024 $12.99   Add to cart

Exam (elaborations)

Second Year IEC Final Exam Questions and Answers 2024

 14 views  0 purchase
  • Course
  • Second Year IEC
  • Institution
  • Second Year IEC

Anex _____ in the NEC contains examples of load calculations for dwellings. -answer- D Which of the installations listed below would be a wet location? -a receptacle installed on the exterior wall of a building - a run of PVC conduit installed on a fishing pier -a luminaire installed on a par...

[Show more]

Preview 2 out of 8  pages

  • September 18, 2024
  • 8
  • 2024/2025
  • Exam (elaborations)
  • Questions & answers
  • second year iec
  • Second Year IEC
  • Second Year IEC
avatar-seller
PossibleA
Second Year IEC Final



Second Year IEC Final Exam Questions
and Answers 2024
Anex _____ in the NEC contains examples of load calculations for dwellings. -answer-
✔D

Which of the installations listed below would be a wet location?
-a receptacle installed on the exterior wall of a building
- a run of PVC conduit installed on a fishing pier
-a luminaire installed on a parking lot pole -answer- ✔all of these

Which of the following is an example of a bare conductor?
- a 12 awg THHN copper wire
- the bare ground wire contained within romex (NM cable) sheathing
-the bare aluminum wire twisted with triplex -answer- ✔the bare aluminum wire twisted
with triplex

Which of the following statements is TRUE for an individual (or dedicated) branch circuit
that is run in a conduit with other circuits? -answer- ✔it can share a neutral with another
circuit

Equipment designed to open circuits under ____ shall have an interrupting rating not
less than the nominal circuit voltage and the current that is available at the line side of
the equipment.
- short circuit
-overload
-ground fault -answer- ✔all of these

The NEC permits the insulation for an ungrounded conductor to be _____ in color.
- orange
-black
-brown
-yellow -answer- ✔any of these

Which of the following locations requires that a three-way switch be installed at the
lower landing and another three-way switch be installed at the upper landing to control
the stair way lighting between the 1st and 2nd floors? -answer- ✔a townhome

A 175- amp breaker protects a feeder that originates in a 277/480-volt, 3-ph, 4 wire
service panel in an office building. Which of the following conductors is the smallest size
permitted for the feeder ? -answer- ✔2/0



Second Year IEC Final

, Second Year IEC Final


A 200-amp breaker protects a feeder that originates in a 120/240 volt, 3 ph, 4 wire
service panel in a movie theatre. Which of the following THHN/THWN conductors is the
smallest size permitted for the feeder ? -answer- ✔3/0

The maximum number of 3-pole circuit breakers used as service disconnects permitted
in a 3 phase panelboard is ______. -answer- ✔6

Which of the following are characteristics of THHN/THWN insulation?
- heat-resistant
- a nylon outer covering or some equivalent
- flame retardant
-moisture-resistant -answer- ✔all of these

For the purpose of determining the number of current-carrying conductors in a cable or
conduit, the neutral _____ counted when the branch circuit is 120/240-volt, 1 phase, 3
wire connected to a 120/240-volt, 3 phase delta, 4 wire panelboard. Each of the two
circuits carries 16 amps and serves resistive (linear) loads. -answer- ✔is not

Where a 120/240 volt, 1 phase, 3 wire multiwire branch circuit is connected to a "split-
wired" duplex receptacle in a barber shop, the branch-circuit OCPD/disconnect is
permitted to be ______
i. two single-pole circuit breakers without handle ties
ii. two single-pole circuit breakers with identified handle ties
iii. a 2-pole circuit breaker -answer- ✔ii or iii only

Which of the following is a type of circuit condition?
i.short circuit
ii. overload -answer- ✔i and ii

A 20-amp multiwire branch circuit is connected to breakers 1 and 3 in a 120/208 volt 3
phase 4 wire panelboard. _____ if the "hot" from breaker 3 and the neutral are
connected to a 2000-watt lighting fixture load. -answer- ✔The load will operate normally
and the breaker will not trip

When ____ touch together this is a short circuit.
-i. two ungrounded circuit conductors
- ii.an ungrounded and a grounded circuit conductor
- iii. an ungrounded circuit conductor and the metal conduit. -answer- ✔i or ii only

You are going to pull in three dedicated (individual) branch circuits into one conduit.
Each circuit supplies power to a 120-volt load. The ungrounded conductors will be
connected to breakers 2,4 and 6 in a 120/240 volt single phase 3- wire panel board. Per
the NEC, the fewest number of neutral conductors you can install for the branch circuit
is _______. -answer- ✔2


Second Year IEC Final

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller PossibleA. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?

No, you only buy these notes for $12.99. You're not tied to anything after your purchase.

Can Stuvia be trusted?

4.6 stars on Google & Trustpilot (+1000 reviews)

72042 documents were sold in the last 30 days

Founded in 2010, the go-to place to buy study notes for 14 years now

Start selling
$12.99
  • (0)
  Add to cart