___ is the refrigerant that requires special conditions - Answer -R-717 (Ammonia)
___ shall be used in square throat elbows in both return and supply duct: - Answer -Turning vanes
A blower fan used for the ...
HVAC Journeyman Prep Test Questions
with Verified Answers Download and
Get a Full Score
___ is the refrigerant that requires special conditions - Answer -R-717 (Ammonia)
___ shall be used in square throat elbows in both return and supply duct: - Answer -Turning vanes
A blower fan used for the purpose of distributing supply air to a room, space, or area is a: (A)Air-handling
unit (B)Return fan (C)Make-up fan (D)Exhaust fan - Answer -Air handling unit (IMC Chapter #2)
A chimney for a low heat appliance must withstand a continuous flue gas temperature not exceeding
___: (A)1000 (B)1800 (C)800 (D)1200 - Answer -1000
A chimney for a low-heat appliance must withstand a continuous flue gas temperature not exceeding
___: (A)1000 (B)1800 (C)800 (D)1200 - Answer -1000
A chimney for a medium-heat appliance shall extend at least ___ feet higher than any portion of any
building within ___ feet: (A)5',25' (B)2',10' (C)10',25' (D)3',10' - Answer -10',25' (Fuel Gas Code,
12.6.2.2)
A chimney for a residential type or low-heat appliances shall exceed at least ___ feet above the highest
point where it passes through the roof of a building? (A)5' (B)2' (C)10' (D)3' - Answer -3' (Fuel Gas
Code, 12.6.2.1)
A cooling coil is to be installed in a duct system containing an existing furnace heat exchanger. Unless
otherwise listed, the code requires the air flows first through: (A)The heat exchanger (B)A diverter unit
(C)The cooling coil (D)A bypass duct - Answer -The heat exchanger (Fuel Gas Code, 10.10.6.3)
A direct vent appliance with an input over 50,000BTU/hr shall have at least ___ inches from any air
opening into a building: (A)12" (B)6" (C)18" (D)9" - Answer -12"
A direct vent appliance with an input over 50,000BTU/hr, shall have at least ___ inches from any air
opening into a building: (A)12 (B)6 (C)18 (D)9 - Answer -12
A duct system for hazardous exhaust shall be required whenever a flammable vapor is present in
concentrating ___ percent of its lower flammability limit: (A)15% (B)20% (C)30% (D)25% - Answer -
25%
A fuel gas system is designed for an operating pressure of 5PSI, what is the lowest test pressure?
(A)10PSI (B)15PSI (C)7.5PSI (D)2.5PSI) - Answer -7.5PSI (Fuel Gas Code, 8.1.4.2)
A galvanized 12" vent for a non-residential low-heat appliance shall have a minimum thickness of ___
inches: (A)0.019 (B)0.023 (C)0.029 (D)0.034 - Answer -0.029
, A listed smoke damper designed to resist the passage of smoke shall be provided at each point in a duct
or air transfer opening penetrates a: (A)smoke barrier wall (B)fire rated wall (C)interior wall (D)corridor
wall - Answer -Corridor wall (IMC 607.5.4)
A non-load bearing stud may be notched ___% of its depth: (A)15% (B)25% (C)30% (D)40% -
Answer -40% (IMC 302.3.2)
A Pair of hanger straps at 2.2m spacing for 1000 x 1000 mm duct should be: (A)25.4 x 1 (B)25.4 x 1.31
(C)38.1 x 1.61 (D)25.4 x 1.61 - Answer -25.4 x 1.31
A Pair of hanger straps spaced at 5' for a 30" X 30" duct should be: (A)1" x 8Ga. (B)1" x 20Ga. (C)1" x
22Ga. (D)1" x 24Ga. - Answer -1" x 22Ga.
A Permit is not required if a self-contained refrigerant system has ___lbs or less of refrigerant: (A)5lbs
(B)10lbs (C)8lbs (D)4lbs - Answer -10lbs (IMC 106.2.7)
A Permit to accomplish work may be extended a maximum of how many times? (A)1 (B)2 (C)3 (D)4 -
Answer -1 (IMC 106.4.4)
A roof jack must be flashed a minimum of ___ inches above a roof: (A)8" (B)12" (C)6" (D)4" -
Answer -8" (SMACNA 3.3)
A type 1 hood shall have what minimum clearance to combustable materials? (A)14" (B)6" (C)18" (D)10"
- Answer -18" (IMC 507.2.6)
A Type B or a Type L gas vent shall terminate at least _____ feet in vertical height above the highest
connected appliance draft hood or flue collar: (A)2' (B)5' (C)8' (D)10' - Answer -5' (Fuel Gas Code,
12.6.5.1.2)
A type L gravity vent system for a gas-fired appliance shall terminate what minimum distance above the
highest vent collar it serves? (A)3' (B)5' (C)7' (D)9' - Answer -5'
A type L vent requires ___ inches of clearance to combustibles: (A)9" (B)18" (C)24" (D)12" -
Answer -9"
A vent connector shall be installed without any dips or sags and shall slope upward toward the vent at
least ___ inch per foot: (A)1/8" (B)1/4" (C)1" (D)1/2" - Answer -1/4"
A vented wall furnace shall be installed so that a door cannot swing within what distance of the furnace
air inlet or outlet? (A)9" (B)12" (C)6" (D)3" - Answer -3"
A wall mounted canopy hood used with a heavy duty cooking appliance shall have a minimum CFM per
linear square foot/hood of: (A)550 (B)400 (C)300 (D)None of the above - Answer -400 (IMC
507.5.2)
A wall mounted canopy hood used with heavy duty cooking appliance shall have a minimum CFM per
linear foot of hood of: (A)550CFM (B)400CFM (C)300CFM (D)500CFM - Answer -400CFM (IMC
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller Eddiebeststudy. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $7.49. You're not tied to anything after your purchase.