NYC MASTER ELECTRICIAN EXAM2024
WITH 100% ACCURATE SOLUTIONS
Type ____ is multiconductor cable identified for use as underground
service entrance cable. - Precise Answer ✔✔Type USE cable
Knife switch rated for more than 1200 Amps at 250Volts or less -
Precise Answer ✔✔Can be used only as isolating switch, shall not be
opened under load
Track lighting with outlets in a bathroom is not allowed because ? -
Precise Answer ✔✔Track lighting has receptacle
Where internal combustion engines are used as the prime motor, an on
site fuel supply shall be provided with an on premise fuel supply
sufficient for not less than ____ hours full demand operation of the
system - Precise Answer ✔✔6 hours
Fixed in place X-ray equipment properly supplied by a branch circuit
rated at not over ____ amperes shall be permitted to be supplied through
a suitable attachment plug cap and hard service cable cord. - Precise
Answer ✔✔30 Amps
Where skin effect exist the ferromagnetic envelope shall be bonded at
____. - Precise Answer ✔✔Both ends
,GFCI protection at a carnival is not required for equipment at circuit if
the receptacle is of the ____type. - Precise Answer ✔✔Locking
The maximum voltage drop from service point to the last over-current
device in a dwelling unit? - Precise Answer ✔✔4%
Which of the following statements best describe the grounding
requirement for central vacuum outlet - Precise Answer ✔✔Accessible
non current carrying metal parts are required to be connected to an
equipment grounding conductor.
In healthcare facilities, patient bed receptacles located in general care
areas shall be supplied by at least two branch circuits, which
____permitted to originate from two separate transfer switches on the
emergency system - Precise Answer ✔✔Are permitted
Patient care areas of healthcare facilities ____ areas such as business
offices, corridors, lounges ,day rooms, or similar areas - Precise Answer
✔✔Do not include
The patient care area is any portion of the healthcare facility where
patients are intended to be ____or ____. - Precise Answer ✔✔Examined
or treated
,Each general care area patient bed location in a healthcare facility must
be provided with four ____ or ____ duplex receptacles - Precise Answer
✔✔Single or two
A hospital is a building or portion thereof used for medical,
psychiatric,obstetrical , or surgical, care on a 24 hour basis of ____ or
more patients - Precise Answer ✔✔Four
Where installed to reduce electrical noise for electronic equipment,
electrical continuity of the metal raceways shall not be required and
metal raceway can terminate a (an) ____ nonmetallic fitting or spacer on
electronic equipment - Precise Answer ✔✔Listed fitting
Feeder and branch circuit conductors within ____ inches of a Ballast
shall have an insulation temperature rating not lower than 90°C (194°F)
unless supplying a luminaiere marked as suitable for a different
insulation temperature - Precise Answer ✔✔3 inches
Manufactured wiring systems constructed with type MC cable shall be
supported and secured at intervals not exceeding ____ ft. - Precise
Answer ✔✔6 ft
Where a main bonding jumper or a system bonding jumper is a screw
only the screw shall be identified with a ____ that shall be visible with
the screw installed - Precise Answer ✔✔Green finish
, Plug fuses a 15 amperes and lower rating shall be identified by a ____
configuration of the window, cap, or other prominent part to distinguish
them from fuses of higher ampere rating - Precise Answer ✔✔Hexagon
The load for household electric clothes dryer's in a dwelling unit(s) shall
be either ____ watts (volt-amperes) or the nameplate rating, which ever
is larger, for each dryer served ? - Precise Answer ✔✔5000 watts
Service conductors installed as unjacketed multiconductor cable shall
have a minimum clearance of ____ windows that are designed to be
opened, doors, porches, stairs fire escape or similar locations. - Precise
Answer ✔✔3 ft (36 inches)
—— Cartridge fuses of the renewable type shall be permitted to be used
only for replacement in existing installation is where there is no
evidence of over-fusing or tampering. - Precise Answer ✔✔Class H
Branch circuit conductors within ____inches of the ballast shall have an
insulation temperature rating not lower it 90°C 194°F - Precise Answer
✔✔3" inches
The minimum radius of a field bend on trade size 1 "1/4 RMC is ____. -
Precise Answer ✔✔8
In a dwelling unit which appliance is allowed to have a 24"inch cord
with Attachment ground plug ? - Precise Answer ✔✔Combination range
hood/microwave oven
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller YANCHY. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $16.49. You're not tied to anything after your purchase.