NETA ETT Certified Level 3 Questions and Answers Graded A+ A newly installed 4160V emergency generator has an insulation resistance value of 150 Megohms after one minute with an equipment temperature of 32 degrees C. Is this value acceptable per NETA standards? No NETA ATS-2017 Table 10...