Where K=12.9, what is the approximate voltage-drop on a circuit where an 80-ampere,
240-volt, single-phase load is supplied with size 3 AWG copper conductors with THWN
insulation, and placed 200 feet from a panelboard?
voltage-drop formula
VD=2KID VD=2 x 12.9 x 80amps x 200ft. =7.84
CM 52.620 CM
Given the following information, what is the maximum approximate distance a single-
phase, 240-volt, 42-ampere load can be located from a panelboard?
*copper conductors - K = 12.9
*size 8 AWG THWN/THHN conductors are used
*limit voltage drop to 3%
Distance formula
1st. find allowable VD - 240volts x 3% = 7.2volts
D=CM x VD
D=16,510 x 7.2=118,872=109.7feet
2 x K X I 2 X 12.9 X 42
What is the minimum allowable trade size intermediate metal conduit (IMC) required to
contain a total of ten (10) copper THW conductors in a 20ft run, five (5) size 1 AWG and
five (5) size 3 AWG?
*(Pg. 70-684) - answer2-1/2 Inches
size 1 AWG THW=.1901 sq. in. x 5=.9505 sq. in.
size 3 AWG THW=.1134 SQ. IN. x 5=.537 sq. in.
total=1.5175 sq. in.
*NOTE: A trade size 2-1/2 in. IMC with an allowable 40% fill of 2.054 sq. in. should be
selected.
If more than 2 conductors are used in a tube of EMT conduit, the total interior area that
can be filled is no more than ______ percent.
, *(Pg. 70-680) - answer40%
What is the maximum cross-sectional value that conduit nipples under 24 inches long
may be filled?
*(pg. 70-678) - answer60%
(4) Where conduit or tubing nipples having a maximum length not to exceed 600 mm
(24 in.) are installed between boxes, cabinets, and similar enclosures, the nipples shall
be permitted to be filled to 60% of their total cross-sectional area, and 310.15(B)(3)(a)
adjustment factors need not apply to this condition
True or False:
The raceway fill limitations detailed in 300.17 will apply to coaxial cables. - answerFalse
The raceway fill requirements of chapters 3 & 9 shall not apply to coaxial cables.
A bonding jumper not smaller than ________ AWG copper or equivalent must be
connected between the radio and TV equipment grounding electrode and the power
grounding electrode system when they are separate. - answer6 AWG
A bonding jumper not smaller than 6 AWG copper or equivalent shall be connected
between the radio & TV equipment grounding and the power grounding electrode
system at the building or structure served where separate electrodes are used.
How far must the separation be between any light, power, or Class 1 conductors or
radio & TV conductors, and underground antenna conductors for radio & TV receiving
equipment? - answer12 inches
underground conductors shall be separated at least 300mm (12 in.) from conductors of
any light or power circuits or Class 1 circuits.
Unless otherwise permitted, communications cables and wires must be separated at
least 2 in. from which circuit conductors? - answerPower, lighting, or Class 1
Communications wires and cables shall be separated at least 50mm (2in.) from
conductors of any electric light, power, Class 1, non-power-limited fire alarm, or
medium-power network-powered broadband communications circuits.
The abbreviation TYP represents: - answerTypical
What does the abbreviation A.F.F. represent? - answerAbove Finished Floor
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller julianah420. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $17.99. You're not tied to anything after your purchase.