A three dimensional fire often involves static flammable liquid. true or false - Answers-
false. 3D firess unvolve flammable liquid in motion as well as both horizontal and
vertical surfaces.

Class A fire extinguisher - Answers- are ok for wood, paper, some plastics and textiles.
They offer the coating effects of dry chemicals.

Dry chemical stored pressure fire extinguishers: - Answers- should be removed or
replaced at their next 6 year maintenance or hydrostatic test interval.

B:C - Answers- Talking about UL rating, the _____ rating refers to the amount of sq
footage an extinguisher covers

Class B fire extinguishers cannot handle flammable liquid - Answers- False

employees must be trained in proper use of all portable fire extinguishers according to -
Answers- CRF29

monthly - Answers- you need to have portable fire extinguishers VISUALLY inspected
at least _____ according to 29 CFR 1910.157 (e) (2)

Class A/B fire extinguishers - Answers- should NOT be used forfire that involves live
electrical equipment

annually - Answers- Water or steam fire extinguishers need to be discharged,
dissassembled and inspected at least:

3.5 ft - Answers- An extinguisher weighing over 40 lbs should be installed so the top is
no more than __ from the ground

50 ft. - Answers- OSHA specified maximum travel distance to an extinguisher for Class
B

6 yrs - Answers- dry chem extinguishers requiring 12 yr hydrostatic test must be
emptied for maintenance procedures every

A rated UL extinguishers = how many gallons of water? - Answers- 1.25

C - Answers- Class ____ fire extinguishers use electrically nonconductive extinguishing
agents

,Every 5 years - Answers- Cartridge operated water based portable extinguishers need
hydrostatic testing

stored pressure type extinguishers need need INTERNAL examination : - Answers-
never

5 ft above the ground - Answers- extinguishers weighing 40 lbs or less must be
installed so top of canister is no more than _____

K - Answers- class ___ extinguishers are for fires involving cooking media

75 ft - Answers- OSHA specified max travel distance for Class A is ______

C - Answers- proper UL rating to use on electrically energized equipped

Class K - Answers- work on the principle of saponification

Obstacle Type Fires - Answers- involve flammable liquid on a horizontal surface w/ the
presence of a solid object creating a barrier

4 inches - Answers- extinguishers must be installed at least _____ from the ground

Obstacle Type Fires - Answers- may take place in flammable liquid storage caninets,
dip tank process areas, etc.

Must Be Weighed - Answers- To make sure the pressure gauges of CO2 extinguisher
are showing adequate pressure, what must you do?

5 yrs - Answers- Wetting agent portable extinguishers must be hydrostatic tested every
_____

After recharge - Answers- leak tests on stored pressure extinguishers must be
performed

cannot - Answers- how do u convert fire extinguishers from 1 type to another?

any remaining dry chemical in a discharged extinguisher - Answers- may be reused
only if checked for proper type, contamination, and condition. closed recovery system
needs to be used!

New extinguishers needing charge in the field - Answers- do not need to have any
verification of service collar installed

you cannot - Answers- how do u have an extinguisher converted to use a different type
of extinguishing agent

, annually - Answers- the gauge used to set the regulated source of pressure needs to
be calibrated

annually - Answers- pump tank calcium chloride based antifreeze typesof extinguishers
need to be recharged

75 ft. - Answers- OSHA specified max distance to extinguisher for Class D

weighing - Answers- when you recharge, the amount of recharge agent to use should
be verified by

Aqueous Film Forming Foam (AFFF) - Answers- these types of extinguishers must
have hydrostatic testing every 5 yrs

annually - Answers- The wetting agent in stored pressure wetting agent extinguishers
must be replaced

3 yrs - Answers- The premixed agent in liquid charge-type AFFF and FFFP
extinguishers must be replaced every

cylinder-operated extinguishers - Answers- do not need to have any verification of
service collar installed

False - Answers- you are free to mixmultipurpose dry chemicals w/ alkaline based dry
chemicals

must be avoided - Answers- subsurface injection of wet chemical extinguishing agents
into hot cooking media

False - Answers- You should NEVER place extinguishers in cabinets or wall recesses.

5 yrs - Answers- how often must CO2 portable extinguishers go through hydrostatic
testing?

Special Hazards - Answers- Pressurized gas fires and pressurized flammable liquids.

Type B, Special Hazards - Answers- Type ___ extinguishers w/ agents other than dry
chemicals are not very effective on ______

Do not attempt - Answers- How do you filed adjust regulators that are utilized on
wheeled fire extinguishers?

False - Answers- You do not need to keep permanent file record for each extinguisher
unless it has been in use for over 1 1/2 yrs

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller Greaterheights. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?

No, you only buy these notes for $11.09. You're not tied to anything after your purchase.

Can Stuvia be trusted?

4.6 stars on Google & Trustpilot (+1000 reviews)

75759 documents were sold in the last 30 days

Founded in 2010, the go-to place to buy study notes for 14 years now

Start selling
$11.09
  • (0)
  Add to cart