100% satisfaction guarantee Immediately available after payment Both online and in PDF No strings attached
logo-home
Fire pump Exam|45 Complete Questions and Answers $8.49   Add to cart

Exam (elaborations)

Fire pump Exam|45 Complete Questions and Answers

 4 views  0 purchase
  • Course
  • Fire pump
  • Institution
  • Fire Pump

Fire pump Exam|45 Complete Questions and Answers

Preview 2 out of 5  pages

  • November 5, 2024
  • 5
  • 2024/2025
  • Exam (elaborations)
  • Questions & answers
  • Fire pump
  • Fire pump
avatar-seller
Nursephil2023
Fire pump Exam|45 Complete Questions
and Answers
500 - -pumps other than those specified in this standard and having
different design features shall be permitted to be installed where such
pumps are listed by a testing laboratory. these pumps shall be limited to
capacities of less than _____ gpm.

- true - -Any source of water that is adequate in quality, quantity, and
pressure shall be permitted to provide the supply for a fire pump.

- 100 - -Where maximum flow available from the water supply cannot
provide a flow of 150 percent of the rated flow of the pump , but the water
supply can provide the greater of _____ percent of rated flow or the
maximum flow demand of the fire protection systems, the water supply shall
be deemed to be adequate. in this case, the maximum flow shall be
considered the highest flow that the water supply cannot achieve.

- steam turbines - -acceptable drivers for pumps at a single installation shall
be electric motors, diesel engines,_______, or a combination thereof.

- 3.5" - -A pressure gauge having a dial not less than_______ in diameter
shall be connected near the discharge casting with a nominal .25 in. gauge
valve.

- 200 - -The dial on the gauge on the discharge side of the pump shall
indicate pressure to at least twice the rated working pressure of the pump
but not less than _____ psi.

- compound - -Where the minimum pump suction pressure is below 20 psi
under any flow condition, the suction gauge shall be a __________ pressure
and vacuum gauge.

- Engine Driven - -unless the requirements if 4.11.1.7 are met, each pump
shall have an automatic relief valve listed for the fire pump service installed
and set below the shutoff pressure at minimum expected suction pressure. I.
4.11.1.7 which pumps do not require automatic relief valve.

- 1" - -The automatic relief valve shall have a nominal size of .75 in. for
pumps with a rated capacity not exceeding 2500 gpm and have a nominal
size of ______ for pumps with a rated capacity of 3000 gpm to 5000 gpm.

- 50' - -Fire pump units that are outdoors shall be located at least ______
away from any buildings and other fire exposures exposing the building.

, - True - -Fire pump buildings or rooms enclosing diesel engine pump drivers
and day tanks shall be protected with an automatic sprinkler system
installed in accordance with NFPA 13, Standard for the installation of
sprinkler systems.

- bypass - -Where the suction supply is of sufficient pressure to be of
material value without the pump, the pump shall be installed with a ______.

- OS&Y - -A listed ______ gate valve shall be installed in the suction pipe. No
other kind of valves shall be installed in the suction piping within 50' of the
fire pump.

- eccentric - -Where the suction pipe and pump suction flange are not of the
same size, they shall be connected with an _______ tapered reducer or
increase installed in such a way as to avoid air pockets.

- Double intake screens - -Where the water supply is obtained from an open
source such as a pond or wet pit, the passage of materials that might clog
the pump shall be obstructed. ____________ shall be provided at the suction
intake. Screens shall be removable or an situ cleaning shall be provided.

- check valve - -A listed ______ or backflow preventer shall be installed in the
pump discharge assembly.

- Butterfly - -Where pumps are installed in a series, a __________ valve shall
not be installed between pumps.

- check valve - -When a low suction throttling valve is used, it shall be
installed according to manufacturers reccomendations in the piping between
the pump and the discharge _________.

- 1" - -in fire pump assemblies a clearance of not less than _______ shall be
provided around pipes that pass through walls or floors.

- pressure relief valve - -Where a diesel engine fire pump is installed and
where a total of 121 percent of the net rated shutoff (churn) pressure plus
the maximum static suction pressure, adjusted for elevation, exceeds the
pressure for which the system components are rated, a ________ shall be
installed.

- check valve - -The relief valve shall be located between the pump and the
pump discharge _________ and shall be so attached that it can be readily
removed for repairs without disturbing the piping.

The benefits of buying summaries with Stuvia:

Guaranteed quality through customer reviews

Guaranteed quality through customer reviews

Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.

Quick and easy check-out

Quick and easy check-out

You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.

Focus on what matters

Focus on what matters

Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!

Frequently asked questions

What do I get when I buy this document?

You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.

Satisfaction guarantee: how does it work?

Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.

Who am I buying these notes from?

Stuvia is a marketplace, so you are not buying this document from us, but from seller Nursephil2023. Stuvia facilitates payment to the seller.

Will I be stuck with a subscription?

No, you only buy these notes for $8.49. You're not tied to anything after your purchase.

Can Stuvia be trusted?

4.6 stars on Google & Trustpilot (+1000 reviews)

75632 documents were sold in the last 30 days

Founded in 2010, the go-to place to buy study notes for 14 years now

Start selling
$8.49
  • (0)
  Add to cart