Where conduits enter a floor-standing switchboard or panelboard at the bottom, the conduits including their end fittings, shall not rise more than _____ above the bottom of the enclosure.
a) 6 inches
b) 4 inches
c) 2 inches
d) 3 inches - ANSWERD: 3 inches
Ref: 408.5
When installed on the ...
Where conduits enter a floor-standing switchboard or panelboard at the bottom, the conduits
including their end fittings, shall not rise more than _____ above the bottom of the enclosure.
a) 6 inches
b) 4 inches
c) 2 inches
d) 3 inches - ANSWERD: 3 inches
Ref: 408.5
When installed on the service of a building or structure, a type 2 SPD (TVSS) shall be connected
_____.
a)on the line side of the service disconnect overcurrent device
b) on the load side of the service disconnect overcurrent device
c) on the meter housing
d) at the final overcurrent device - ANSWERB: on the load side of the service disconnect overcurrent
device
Ref: 285.24(A)
A detached garage supplied from a dwelling with a three-wire feeder of size 4/0 AWG aluminum USE
cable with a 200-ampere rated circuit breaker for overcurrent protection requires a MINIMUM size
copper grounding electrode to a concrete encased electrode of _____ AWG.
a) 8
b) 6
c) 4
d) 2 - ANSWERC: 4
Ref: 250.52(A)(3)
, When a raceway is run from the interior to the exterior of a building, the raceway shall _____.
a) be rigid metal conduit (RMC)
b) be rigid polyvinyl chloride conduit (PVC)
c) be sealed with an approved material
d) have an explosion-proof seal - ANSWERC: be sealed with an approved material
Ref: 300.7(A)
A disconnecting means shall be provided on the supply side of all fuses in circuits having a voltage of
at LEAST _____ volts to ground.
a) 120
b) 250
c) 150
d) 277 - ANSWERC: 150
Ref: 240.40
Ref: 501.15(A)(1)
Surface-mounted incandescent luminaires installed on the wall above the door or on the ceiling of a
clothes closet shall have a clearance of at LEAST ____ between the luminaire and the nearest point
of storage.
a) 6 inches
b) 8 inches
c) 18 inches
d) 12 inches - ANSWERD: 12 inches
Ref: 410.16(C)(1)
The NEC considers the area around the fuel dispensing pumps at a service station to be a hazardous
location. This area extends a height of 18 inches above grade, and up to a distance from the
enclosure of the dispensing pump of _____.
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller papersmaster01. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $15.49. You're not tied to anything after your purchase.