What is the first thing a tech should do when arriving at a no combustion call? - CORRECT
ANSWER- Ask how many times the customer reset the unit.
What is the best long term solution for preventing a clogged nozzle? - CORRECT...
Oil Burner License UPDATED ACTUAL
Exam Questions and CORRECT Answers
What is the first thing a tech should do when arriving at a no combustion call? - CORRECT
ANSWER- ✔✔Ask how many times the customer reset the unit.
What is the best long term solution for preventing a clogged nozzle? - CORRECT ANSWER-
✔✔-Remove any underground storage tanks.
-Install a quality oil filter.
-Cut the suction line 10" above the tank outlet to prevent sludge.
Hot water and steam valves are interchangeable. - CORRECT ANSWER- ✔✔False
When in the presence of a flame, a cad cell normally reads.. - CORRECT ANSWER-
✔✔300-1000 ohms
If a pump is used to bring oil to a level higher than the tank, an oil safety valve is required. -
CORRECT ANSWER- ✔✔True
On a call where a hydronic heat system is putting out too much heat on the stack, the issue
may be.. - CORRECT ANSWER- ✔✔-Too much draft.
-Not enough combustion air in the equipment room.
-Air leakage into chamber.
A high CO2 reading is caused by.. - CORRECT ANSWER- ✔✔Incomplete combustion
An often overlooked cause of a high CO2 reading is.. - CORRECT ANSWER- ✔✔Not
enough combustion air in the equipment room.
When multiple pumps are wired together in a heating system, they should be wired in.. -
CORRECT ANSWER- ✔✔parallel
,In a series circuit.. - CORRECT ANSWER- ✔✔Current has one path.
When 2 burners are connected to the same chimney.. - CORRECT ANSWER- ✔✔Sufficient
draft must be obtained to operate both units.
The ignition transformer is located.. - CORRECT ANSWER- ✔✔In the primary control.
When safeties are wired in series one safety will affect the operation of the others. -
CORRECT ANSWER- ✔✔True
A stack switch is no longer allowed to be installed or replaced because.. - CORRECT
ANSWER- ✔✔It's safety cutout time is higher than what is now required.
What is a power venter and what does it do? - CORRECT ANSWER- ✔✔An electrical
device that sends fluid gases into the chimney connector.
A burner in a confined space using 1 GPH of #2 fuel oil requires what size permanent
opening for combustion air? - CORRECT ANSWER- ✔✔140"
The difference between an adjustable flame retention burner and a fixed flame retention
burner is? - CORRECT ANSWER- ✔✔Air inlets can be adjusted
Ignitor position can be adjusted
Fuel can be adjusted
Oil tank design, construction, installation and testing shall be in accordance with.. -
CORRECT ANSWER- ✔✔527 CMR 9.0
Heat is a form of.. - CORRECT ANSWER- ✔✔Energy
, If a burner is operational but the circulator pump isn't running.. - CORRECT ANSWER-
✔✔The pump relay is not working correctly
A method of dealing with low viscosity/cold temps with #2 oil? - CORRECT ANSWER-
✔✔Increase pump pressure/ decrease nozzle size
What is needed at the outlet of an oil tank? - CORRECT ANSWER- ✔✔Thermal safety valve
Where do you obtain an installation permit for oil burners? - CORRECT ANSWER- ✔✔Fire
Dept
How many Btu's approximately in 1 gal of #2 fuel oil? - CORRECT ANSWER- ✔✔140,000
btu's
Solid state ignition is superior to spark because - CORRECT ANSWER- ✔✔It is not affected
by reduced voltage
What is an installation? - CORRECT ANSWER- ✔✔The complete setting in place, ready for
operation, of an oil burner appliance together with its accessories and equipment.
How far must a power vent terminate from an opening or window? - CORRECT ANSWER-
✔✔4'
A pump in a one pipe system that is full of air can be self purged. - CORRECT ANSWER-
✔✔False
List the minimum size of an oil supply line. - CORRECT ANSWER- ✔✔3/8"
A material with electrons so loose it allows voltage to pass with little or no resistance.. -
CORRECT ANSWER- ✔✔Is a conductor
If a high limit goes off, what does a low water switch do? - CORRECT ANSWER-
✔✔Maintains water temperature
The benefits of buying summaries with Stuvia:
Guaranteed quality through customer reviews
Stuvia customers have reviewed more than 700,000 summaries. This how you know that you are buying the best documents.
Quick and easy check-out
You can quickly pay through credit card or Stuvia-credit for the summaries. There is no membership needed.
Focus on what matters
Your fellow students write the study notes themselves, which is why the documents are always reliable and up-to-date. This ensures you quickly get to the core!
Frequently asked questions
What do I get when I buy this document?
You get a PDF, available immediately after your purchase. The purchased document is accessible anytime, anywhere and indefinitely through your profile.
Satisfaction guarantee: how does it work?
Our satisfaction guarantee ensures that you always find a study document that suits you well. You fill out a form, and our customer service team takes care of the rest.
Who am I buying these notes from?
Stuvia is a marketplace, so you are not buying this document from us, but from seller MGRADES. Stuvia facilitates payment to the seller.
Will I be stuck with a subscription?
No, you only buy these notes for $9.99. You're not tied to anything after your purchase.